Plastic Frame V Bank Filter V/W Type Air Purifier Medium Efficiency:F6,F7,F8,F9
Detail
Application: Air intake for gas turbines, compressors and large engines.
Type: High efficiency, incinerable compact filter.
Frame: Polypropylene and ABS.
Gasket: Expanded polyurethane placed on the downstream side (code 01).
Media: Glass fibre paper.
Separator: Hot-melt beads.
Sealant: Polyurethane.
Grid: Glass fibre reinforcement grid placed downstream.
EN 779:2002 efficiency: F7. F8 F9.
EN 1822 efficiency: H10.
Recommended final pressure drop: 600 Pa.
Temperature: 80°C maximum in continuous service.
N.B: Burst pressure: > 7500 Pa.
Optional: Alternative frame materials and size available on request.
Parameter
Nominal size | Actual size | Partition | Flange | Rated air volume |
(inch) | (mm) | (V) | (non/single) | (m3/h) |
W×H×D | W×H×D | | | |
12×24×12 | 287×592×292 | 2V | Single flange | 1200 |
24×12×12 | 592×287×292 | 4V | Single flange | 1200 |
24×20×12 | 592×492×292 | 4V | Single flange | 2200 |
24×24×12 | 592×592×292 | 4V | Single flange | 2700 |
12×24×12 | 305×610×292 | 2V | Non-flange | 1400 |
24×24×12 | 610×610×292 | 4V | Non-flange | 3000 |
Nominal size | Surface air speed | Rated initial resistance | Recommended final resistance |
(inch) | (m/s) | (Pa) | (Pa) |
W×H×D | | F6 | F7 | F8 | F9 | Double initial resistance |
12×24×12 | 2.50 | 110 | 120 | 130 | 140 | Double initial resistance |
24×12×12 | 2.50 | 110 | 120 | 130 | 140 | Double initial resistance |
24×20×12 | 2.50 | 110 | 120 | 130 | 140 | Double initial resistance |
24×24×12 | 2.50 | 110 | 120 | 130 | 140 | Double initial resistance |
12×24×12 | 2.50 | 110 | 120 | 130 | 140 | Double initial resistance |
24×24×12 | 2.50 | 110 | 120 | 130 | 140 | Double initial resistance |